203365A 120 Vac to 220/240 Vac
Conversion Kit For
Electronic Air Cleaners
2. Check the ratings given in the instructions and on
Application
the product to make sure the product is suitable for your
application.
The 203365A Conversion Kit changes the 120 Vac,
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
60 Hz to 220/240 Vac, 50/60 Hz. The kit includes a trans-
former and two screws. The line cord on the air cleaner
must be changed to conduit to complete the conversion.
NOTE: The air cleaner can be completely isolated from
the electrical circuit of the HVAC system unless re-
quired by local code to use same circuit. Any convenient
house circuit can power the air cleaner, regardless of
electrical rating of HVAC system.
MOUNT TRANSFORMER
1. Open access door.
2. Remove and retain the two screws from the front of
the power box.
3. Lift and remove the power box.
4. Remove and retain the two screws from the sides of
the power box. See Fig. 1.
5. Remove the power box cover.
6. Place the transformer on the mounting holes. See
Fig. 2.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condi-
tion.
Fig. 1—Remove power box.
3
2
1
4
M6168
J. H. • Rev. 8-93 • ©Honeywell Inc. 1993 • Form Number 69-0769—
Fig. 3—Internal schematic for electronic air cleaner with 203365A Conversion Kit.
BLACK COLLECTOR
TEST
BUTTON
RED IONIZER
RED
CONTACT
BOARD
5
BLACK
BLACK
BLACK
POWER
SUPPLY
P3
P4
J2
P5
P12
2
2
ORANGE
GREEN
BROWN
J7
P21
4
P14
3
GRAY
1
4
P2
P1
P18
P17
VIOLET
BLACK
TERMINAL STRIP
FRONT
BACK
BLACK
1
1
2
W4 W2
W1 W3
2
3
4
BLACK
TO
W8600E
WALL
PANEL
1
3
3
4
BLACK
BLACK
AIR FLOW SWITCH BOARD
1
2
3
4
5
6
INTERLOCK SWITCH.
6
OUTPUT REDUCTION JUMPER.
L1
L2
AIRFLOW SWITCH DISABLE JUMPER.
220/240 VAC
50/60 HZ
RESISTOR FOR W8600 WASH INDICATION THRESHOLD.
ONE-CELL UNIT SIMILAR, BUT WITH JUST ONE CELL.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M5765A
3
69-0769—1
TOOLS AND EQUIPMENT
Troubleshooting the electronic air cleaner requires:
Checkout
•
Needle nose pliers for stringing ionizer wires and
inserting edge connectors.
WARNING
!
•
Test meter.
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY OR
EQUIPMENT DAMAGE.
The following procedures expose hazardous live
parts. Disconnect from power supply between
checks and proceed carefully. These instructions
are for use by only qualified personnel.
NEON LIGHT (On Power Box)
The neon light is powered through the power supply and
is on when the power supply output voltage is normal.
TEST BUTTON
When pushed, the test button shorts from collector
voltage to ground. The resulting arcing sound indicates that
high voltage is being supplied to the collector. The solid
state power supply controls current flow to the collector.
On air cleaners with a W8600E, the CHECK LED will
come on when the test button is held down.
With all components in place, connect power to the air
cleaner. Turn on the air cleaner switch to energize the
system blower. Check the following points of operation:
1. The neon light next to the on-off switch is on. If a
W8600E is part of the installation, check the wall panel
and make sure the ON LED is lit. The W8600E CHECK
LED will come on if there is a problem with the high
voltage power supply.
2. Turn off the system blower. The neon light should
go off after a few seconds. The neon light indicates that
the air cleaner is energized and the high voltage power
supply is working properly.
CHECK LED (Air Cleaners with W8600E)
The CHECK LED is on the W8600E. It lights to indicate
the following problems: excessive dirt loading (beyond
that required to activate the WASH LED), partial shorting
of the collector, continuous ionizer or collector arcing,
power supply failure, excessive ionizer current, or any
condition causing a major reduction in high voltage.
3. Turn on the system blower. With the air cleaner
energized, push the test button. A snapping sound indi-
cates that the collector voltage is present on the cell. The
W8600E CHECK LED will come on when the test button
is held down.
4. With a multispeed blower, repeat steps 1 through 3
for each fan speed.
POWER BOX
WARNING
!
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY.
Always turn off power and remove access door
before removing power supply or its cover.
5. If operation is not as described, refer to the Electrical
Troubleshooting section.
The solid-state power supply within the power supply
box can be replaced. When troubleshooting indicates a
power supply or solid-state performance indicator prob-
lem, replace the entire power box or replace the power
supply within the box. See Installation Instructions, form
69-0776. See Fig. 1 for power box removal.
Electrical Troubleshooting
WARNING
!
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY OR
EQUIPMENT DAMAGE.
TROUBLESHOOTING PROCEDURE
The electronic air cleaner troubleshooting chart shows
how to quickly isolate a problem in the air cleaner. See
Fig. 4. Although a meter is needed for some steps, the
primary diagnostic tools are the neon light and the test
button.
The following procedures expose hazardous live
parts. Disconnect from power supply between
checks and proceed carefully. These instructions
are for use by only qualified personnel.
4
Fig. 4—Troubleshooting air cleaners with solid-state performance indicator.
START
TO USE THIS CHART:
MAKE SURE ELECTRONIC
CELL(S) ARE CLEAN, DRY
AND PROPERLY INSTALLED.
MAKE SURE PREFILTER(S)
ARE IN CABINET SLOT
1. FOLLOW THE STEPS IN ORDER, DO NOT SKIP AROUND.
2. EACH TIME YOU ISOLATE AND FIX A PROBLEM,
GO BACK TO START.
3. REPEAT ALL THE STEPS UNTIL THE AIR CLEANER
CHECKS OUT OK.
FARTHEST FROM FURNACE.
TURN ON ELECTRONIC AIR
CLEANER AND SYSTEM
FAN.
PUSH TEST BUTTON
AND LISTEN FOR
SNAPPING SOUND.
YES
REPLACE LIGHT/
SWITCH ASSEMBLY.
OFF
NO
CHECK NEON LIGHT.
ON
NO
PUSH TEST BUTTON AND
LISTEN FOR SNAPPING
SOUND.
CORRECT
WIRING.
TURN OFF AIR CLEANER
AND REMOVE CELL(S)
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON
WARNING
THIS STEP EXPOSES
DANGEROUS HIGH
VOLTAGE. ONLY A
QUALIFIED SERVICE
TECHNICIAN SHOULD
ATTEMPT THIS STEP.
YES
WIRING
NOT OK
OFF
OFF
AIR CLEANER.
CHECK ON LED IN
W8600E
CHECK WIRING BETWEEN
W8600E AND AIR CLEANER.
USE MAX. NO. 18 4-WIRE
THERMOSTAT CABLE
CONNECTED 1(G) TO 1(G),
2(Y) TO 2(Y), 3(R) TO 3(R),
AND 4(B) TO 4(B).
2
OFF
ON
CHECK NEON LIGHT.
ON
CHECK FOR CORRECT
INPUT VOLTAGE ACROSS
P1 AND P2 TERMINALS
ON POWER SUPPLY.
DEPRESS AND HOLD DOWN
TEST BUTTON. CHECK
LED IN W8600E
SHOULD COME ON
2
INSPECT CELL(S) FOR:
BENT COLLECTOR
PLATES
•
WIRING OK
NO
YES
ON
BROKEN IONIZER
WIRES
•
FIX
WIRING.
REPLACE
W8600E.
DIRT ON INSULATORS
DAMAGED IONIZER
OR COLLECTOR
CONTACT TABS
•
•
3
TURN OFF AIR CLEANER
AND REMOVE CELL(S)
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON AIR CLEANER.
TURN OFF AIR CLEANER,
REPLACE CELLS(S) AND
DISCONNECT 4 W8600E
LEADS AT AIR CLEANER.
REPLACE ACCESS DOOR.
YES
REPAIR OR
REPLACE
CELL(S).
WASH LED IN W8600E
OFF SHOULD COME ON.
NO
2
ON
TURN ON AIR CLEANER.
PUSH TEST BUTTON
AND LISTEN FOR
WITH OHMMETER,
CHECK FOR SHORT
BETWEEN:
ELECTRONIC AIR CLEANER
AND W8600E ARE OK.
SNAPPING SOUND.
•
CELL FRAME AND
IONIZER SECTION
CELL FRAME AND
NO
YES
•
REPLACE
1
2
FOR POWER SUPPLY REPLACEMENT, SEE FORM 69-0776.
COLLECTOR SECTION
POWER
1
BOX OR
W8600E HAS THREE LIGHT-EMITTING DIODES (LEDS):
ON, WASH, AND CHECK.
CELL
SHORTED
POWER SUPPLY.
3
W8600E OPERATION CAN BE CHECKED SEPARATELY.
SEE W8600E INSTRUCTIONS.
AIR CLEANER OK.
INFINITE
RESISTANCE
REPLACE
CELL.
TURN OFF AIR CLEANER
AND RECONNECT W8600E
LEADS 1(G) TO 1(G), 2(Y)
TO 2(Y), 3(R) TO 3(R), AND
4(B) TO 4(B).
CELL OK.
M5609
5
69-0769—1
Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Home and Building Control
Honeywell Limited—Honeywell Limitée
740 Ellesmere Road
Helping You Control Your World
Scarborough, Ontario
M1P 2V9
QUALITY IS KEY
Printed in U.S.A.
|