QT060
Standby Power Rating
60 kW 60 Hz
Liquid Cooled Gas Engine Generator Sets
GENERAC 2.4L ENGINE
Turbocharged/Aftercooled
Gaseous Fueled
STANDARD EQUIPMENT
•
•
•
•
•
•
•
•
•
•
Mainline circuit breaker
Radiator drain extension
Battery charge alternator
2 Amp static battery charger
Battery and battery cables
Battery rack
Fan and belt guards
Isochronous governor
Flex fuel line
•
•
•
•
•
•
•
•
•
•
•
•
All input connections in one single area
High coolant temperature shutdown
Low oil pressure shutdown
Low coolant level automatic shutdown
Overspeed automatic shutdown
Crank timer
Exercise timer
Oil drain extension
Cool flow radiator
Hour meter
Closed coolant recovery system
UV/Ozone resistant hoses
Watertight state of the art electrical connectors
FEATURES
•
State of the art digital control system with R100 digital
control panel
Watertight electrical connectors
Rodent proof construction
High efficiency, low distortion Generac designed
alternator
Vibration isolated from mounting base
Matching Generac transfer switches engineered and
tested to work as a system
•
•
•
Innovative design and fully prototype tested
UL2200 Listed
•
•
•
Solid state frequency compensated
voltage regulator
•
•
•
•
•
Dynamic and static battery charger
Sound attenuated acoustically designed enclosure
Quiet test for low noise level exercise
Acoustically designed engine cooling system
High flow low noise factory engineered exhaust system
•
•
•
•
All components easily accessible for maintenance
Electrostatically applied powder paint
QT060
OPERATING DATA
kW RATING
QT060
60
ENGINE SIZE
2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
KW
60
60
AMP
208
180
90
CB Size
250
200
277/480V, 3-phase, 0.8 pf
60
100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208/240 3-phase
480V 3-phase
120
141
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)
Natural Gas
(ft3/hr.)
123
Propane
(gal/hr.)
1.34
2.7
cu ft/hr
Exercise cycle
49.3
101
183
255
327
25% of rated load
50% of rated load
75% of rated load
100% of rated load
267
483
672
862
5.0
7.0
9.0
ENGINE COOLING
Air flow (inlet air including alternator and combustion air) ft3/min.
3,280
2.5
270,000
60 (150)
50 (140)
System coolant capacity
US gal.
BTU/hr.
°C (°F)
°C (°F)
Heat rejection to coolant
Max. operating air temp. on radiator
Max. ambient temperature
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
180
SOUND EMISSIONS IN DBA
Exercising at 7 meters
Normal operation at 7 meters
65
72
EXHAUST
Exhaust flow at rated output 60 Hz
Exhaust temp. at muffler outlet
cfm
°F
494
1,050
ENGINE PARAMETERS
Rated synchronous RPM
HP at rated KW
60 Hz
60 Hz
3600
94
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
Altitude Deration
25
77
1% for every 100 m above - m
3% for every 1000 ft. above - ft.
915
3000
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
INTERCONNECTIONS
QT060
kW VOLTS / AMPS LUG SIZE
60
240 1Ø
300
(2) 250 mcm to 2 - 1/0 or
(1) 600 mcm to #4
(2) 250 mcm to 2 - 1/0 or
(1) 600 mcm to #4
#6 to 300 mcm
60
208 3Ø
250
60
60
240 3Ø
480 3Ø
200
100
#6 to 300 mcm
Installation Drawing Ref. No. 0F9577
INSTALLATION LAYOUT
WEIGHT: 1650 lbs.
Generac Power Systems, Inc. • P.O. Box 8, Waukesha, WI 53187 • generac.com
©2008 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0179280SBY/Printed in U.S.A. 09.08
|