Zephyr Ventilation Hood EGL E36AS User Manual

Glide  
EGL-E30AS  
EGL-E36AS  
Modelnumber:  
Numérode modèle: ____________________________________  
Númerodemodelo:  
Serialnumber:  
Numérodesérie : _____________________________________  
Númerodeserie:  
DateofPurchase:  
Dated’achat :  
Fechadecompra:  
_____________________________________  
_____________________________________  
SalesDealer:  
Détaillant:  
Distribuidorr:  
JAN06.0101  
READAND SAVE THESE INSTRUCTIONS  
LISEZ CES INSTRUCTIONS ET CONSERVEZ-LES  
LEAYGUARDE ESTAS INSTRUCCIONES  
 
Important safety Notice .....................................................................4  
Electrical & Installation requirements .............................................5  
Electrical requirements ..............................................................5  
Before installing the hood ...........................................................5  
List of Materials .................................................................................6  
Parts supplied: ...........................................................................6  
Parts not supplied ......................................................................6  
Dimensions and clearances..............................................................7  
Installation Instructions .....................................................................8  
Venting methods ........................................................................8  
Preparation ................................................................................8  
Installation - Ductwork Calculation Sheet ......................................9  
Installation ....................................................................................... 10  
Electrical connection................................................................ 13  
Description of the hood & Controls ................................................ 14  
Controls ................................................................................... 15  
Description of control panel: ..................................................... 15  
Maintenance .................................................................................... 16  
Cleaning ................................................................................... 16  
Grease filter ............................................................................. 16  
Replacing the light bulb: ........................................................... 16  
Trouble Shooting ...................................................................... 17  
Warranty........................................................................................... 18  
List of Part and Accessories............................................................ 19  
3
 
READ AND SAVE THESE INSTRUCTIONS  
CAUTION:  
FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS OR  
VAPORS.  
WARNING  
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:  
A. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.  
B. Before servicing or cleaning the unit, switch power off at service panel and lock service panel disconnecting means  
to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,  
securely fasten a prominent warning device, such as a tag, to the service panel.  
C. Installation Work and Electrical Wiring Must Be Done By Qualified Person(s) In Accordance With All Applicable Codes  
& Standards, Including Fire-rated Construction.  
D. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning  
equipment to prevent back- drafting. Follow the heating equipment manufacturers guideline and safety standards  
such as those published by the National Fire Protection Association (NFPA), the American Society for Heating,  
Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.  
E. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.  
F. Ducted systems must always be vented to the outdoors.  
CAUTION:  
To reduce risk of fire and to properly exhaust air, be sure to duct air outside - do not vent exhaust air into spaces  
within walls, ceilings, attics, crawl spaces, or garages.  
WARNING  
TO REDUCE THE RISK OF FIRE, USE ONLYMETALDUCT WORK.  
Install this hood in accordance with all requirements specified.  
WARNING  
To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Hood WithAny External Solid State Speed Control  
Device.  
WARNING  
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE.  
a) Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may  
ignite. Heat oils slowly on low or medium settings.  
b) Always turn hood ON when cooking at high heat or when flambeing food (i.e. Crepes Suzette, Cherries Jubilee,  
Peppercorn Beef Flambe’).  
c) Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.  
d) Use proper pan size. Always use cookware appropriate for the size of the surface element.  
WARNING  
TO REDUCE THE RISK OF INJURY TO PERSONS, IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOL-  
LOWING:  
a) SMOTHER FLAMES with a close-fitting lid, cookie sheet, or other metal tray, then turn off the gas burner or the electric  
element. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE  
FIRE DEPARTMENT.  
b) NEVER PICK UPA FLAMING PAN - you may be burned.  
c) DO NOT USE WATER, including wet dishcloths or towels - a violent steam explosion will result.  
d) Use an extinguisher ONLY if:  
1)  
2)  
3)  
4)  
You know you have a class ABC extinguisher, and you already know how to operate it.  
The fire is small and contained in the area where it started.  
The fire department is being called.  
You can fight the fire with your back to an exit.  
OPERATION  
a. Always leave safety grills and filters in place. Without these components, operating blowers could catch onto hair,  
fingers and loose clothing.  
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation,  
maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to  
negligence and the warranty of the unit automatically expires due to improper maintenance.  
* NOTE: Please check our website for revisions before doing any custom work.  
4
 
ELECTRICAL REQUIREMENTS  
Important:  
Observe all governing codes and ordinances.  
It is the customer’s responsibility:  
To contact a qualified electrical installer.  
To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA  
70 — latest edition*, or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest  
edition** and all local codes and ordinances.  
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the  
ground path is adequate.  
Do not ground to a gas pipe.  
Check with a qualified electrician if you are not sure range hood is properly grounded.  
Do not have a fuse in the neutral or ground circuit.  
IMPORTANT:  
Save Installation Instructions for electrical inspector’s use.  
The range hood must be connected with copper wire only.  
The range hood should be connected directly to the fused disconnect (or circuit breaker) box through metal electrical  
conduit.  
Wire sizes must conform to the requirements of the National Electrical Code ANSI/NFPA 70 — latest edition*, or CSA  
Standards C22.1-94, Canadian Electrical Code Part 1 and C22.2 No. 0-M91 - latest edition** and all local codes and  
ordinances.  
A U.L.- or C.S.A.-listed conduit connector must be provided at each end of the power supply conduit (at the range hood  
and at the junction box).  
Copies of the standards listed may be obtained from:  
* National Fire Protection Association Batterymarch Park Quincy, Massachusetts 02269  
** CSA International 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575  
BEFORE INSTALLING THE HOOD  
1. For the most efficient air flow exhaust, use a straight run or as few elbows as possible.  
CAUTION: Vent unit to outside of building, only.  
2. At least two people are necessary for installation.  
3. The hood is fitted with Screws and Drywall Anchors suitable for most surfaces, consult a Qualified Installer, check if  
they perfectly fit with your cabinet/wall.  
4. Do not use flex ducting.  
5. COLD WEATHER installations should have an additional backdraft damper installed to minimize backward cold air  
flow and a nonmetallic thermal break to minimize conduction of outside temperatures as part of the ductwork. The  
damper should be on the cold air side of the thermal break.  
The break should be as close as possible to where the ducting enters the heated portion of the house.  
6. Make up air: Local building codes may require the use of Make-Up Air Systems when using Ducted Ventilation  
Systems greater than specified CFM of air movement.  
The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your  
area.  
5
 
PARTS SUPPLIED:  
Blower unit housing  
Hood canopy  
Metal filter x 1  
Halogen light bulb x 2  
Hardware Packet:  
Transition  
Allen spanner x 1  
Lower bracket x 2  
Upper Bracket x 2  
Use, Care and Installation guide  
Template  
Cloth  
2,9x9,5 screws x 2 (to fix the transition)  
4,5x16 screws x 4 (2 to fix the drawer to the bottom of the cabinet + 2 to fix the deflector on top of the cabinet ceiling)  
5x18 screws x 4 (upper/lower brackets adjusting screws)  
3,5x9,5 x 4 (for definitive fixing of upper/lower brackets.  
PARTS NOT SUPPLIED  
Duct, conduit and all tools required for installation.  
Remote Control  
Ductless Recirculating Kit  
to be used only in the Ductless (recirculating) version  
includes: charcoal filter, charcoal filter support and fixing bracket, deflector  
6
 
Ductless (recirculating) version  
7"  
7" 3/8  
Cut out for venting  
system and  
conduit  
1" 1/4  
7" 1/16  
13/16"  
13/16"  
23" 5/16  
9" 1/4  
10"  
1" 1/4  
3" 3/8  
21" 3/4  
Cut out for blower unit  
housing passage  
9" 1/16  
21"  
9"13/1616  
2" 3/4  
30"-36"  
15/16" - 1" 3/4  
7
 
Closely follow the instructions set out in this manual.  
All responsibility, for any eventual inconveniences, damages or fires caused by not complying with the instructions in  
this manual, is declined.  
VENTING METHODS  
The hood is equipped with a transition B for discharge of fumes to the outside (Ducting version).  
Should it not be possible to discharge cooking fumes and vapour to the outside, the hood can be used in the Ductless  
(recirculating) version. Attach a charcoal filter on the internal side of the metal filter and the deflector F directly on the  
transition (Cabinet without ceiling) or at the top of the cabinet. Fumes and vapors are recycled directly through the  
deflector F (Cabinet without ceiling) or by means of a duct connected to the transition B and the deflector F.  
NOTE: For ductless (recirculating) version only: purchase the Ductless Recirculating Kit.  
Minimum Duct Size (Ducting/Ductless version): 6" Round Pipe.  
Roof pitch w/  
Flashing and cap  
Pipe  
F
Pipe  
Pipe  
Side wall cap  
with gravity  
damper  
Ductless  
(recirculating)  
version*  
Ducting version  
PREPARATION  
This hood is designed to be installed inside a cabinet (only Blower unit housing) and fixed at the bottom of the cabinet,  
check that the cabinet, its bottom, the hanging system of the cabinet and the wall where cabinet is installed is strong  
enough to support the hood.  
The inside of the cabinet should be accessible.  
However, a qualified technician must verify suitability of the materials in accordance with the type of cabinet.  
We suggest to mount the cabinet onto the wall after having installed the hood.  
Before making cutouts, make sure there is proper clearance.  
NOTE: For ductless (recirculating) version only: Check that there is enough clearance from ceiling and deflector once  
this last has been mounted to let an easy recirculation of air.  
Hood installation height above cooktop is the users preference. The lower the hood above the cooktop, the more  
efficient the capturing of cooking odors, grease and smoke.  
The hood shall be installed at 24" minimum to 32" above the countertop.  
Check your ceiling height and the hood height maximum before you select your hood.  
8
 
Duct pieces  
Equivalent number  
lenght x used  
Duct pieces  
Equivalent number  
=
Total  
lenght x used  
=
Total  
3 1/4 ” x 10” 1 Ft.  
Rect.,  
x (  
) =  
Ft.  
6" Round  
wall cap  
30 Ft. x (  
) =  
Ft.  
straight  
with damper  
6 ” Round,,  
straight  
1 Ft.  
1 Ft.  
x (  
x (  
) =  
) =  
) =  
Ft.  
Ft.  
Ft.  
6” Round,  
roof cap  
30 Ft. x (  
) =  
) =  
Ft.  
Ft.  
6” Round to 1 Ft. x (  
3 1/4 ” x 10”  
rect.  
7", 8”  
Round,,  
straight  
transition  
3 1/4 ” x 10” 15 Ft. x (  
Rect.90°  
elbow  
6” Round to 16 Ft. x (  
3 1/4 ” x 10”  
rect.  
) =  
Ft.  
transition  
90° elbow  
3 1/4 ” x 10” 9 Ft.  
Rect.45°  
elbow  
x (  
) =  
Ft.  
7", 8" round 15 Ft. x (  
90° elbow  
) =  
) =  
Ft.  
Ft.  
3 1/4 ” x 10” 24 Ft. x (  
Rect.90°  
flat elbow  
) =  
) =  
Ft.  
Ft.  
7", 8" round 9 Ft. x (  
45° elbow  
3 1/4 ” x 10” 30 Ft. x (  
Rect.  
wall cap  
7", 8" Round 30 Ft. x (  
wall cap  
with damper  
) =  
Ft.  
with damper  
3 1/4 ” x 10” 5 Ft.  
Rect.to  
6 ” round  
x (  
) =  
) =  
Ft.  
Ft.  
7", 8"  
Round,  
roof cap  
30 Ft. x (  
8 Ft. x (  
) =  
) =  
Ft.  
Ft.  
transition  
3 1/4 ” x 10” 15 Ft. x (  
Rect.to  
6 ” round  
transition  
90° elbow  
7” Round to  
3 1/4 ” x 10”  
rect.  
transition  
7” Round to  
3 1/4 ” x 10”  
rect.  
transition  
90° elbow  
15 Ft. x (  
) =  
Ft.  
6 ” Round,,  
90° elbow  
15 Ft. x (  
) =  
) =  
Ft.  
Ft.  
Subtotal column 2 =  
Subtotal column 2 =  
6 ” Round,,  
45°elbow  
9 Ft.  
x (  
Total ductwork  
=
Subtotal column 1 =  
Maximum Duct Length: For satisfactory air movement, the total  
duct length should not exceed 100 equivalent feet.  
9
 
1. If possible, disconnect and move freestanding or  
slide-in range from cabinet opening to provide  
easier access to rear wall. Otherwise put a thick,  
protective covering over countertop, cooktop or  
range to protect from damage or dirt. Select a flat  
surface for assembling the unit. Cover that surface  
with a protective covering and place all canopy hood  
parts and hardware in it.  
box.  
Run wires through hole according the National  
Electrical Code or CSA Standards and local  
codes and ordinances.  
There must be enough power supply cable  
from the fused disconnect (or circuit breaker)  
box to make the connection in the hood’s  
Junction box/es.  
2. Remove the metal filter (see paragraph "Mainte-  
nance") top access the inside of the range hood.  
Use caulking to seal all openings on wall.  
Do Not turn on power until installation is  
completed.  
3. Perform any necessary cutout on cabinet and wall  
as per "Dimensions and clearances" paragraph for  
range hood mounting and for vent system and  
conduit passage.  
6. Fit the transition on top of the hood.  
Use the supplied template to perform the cut out on  
cabinet.  
Tape the template on the bottom of the cabinet,  
check that printed arrows match with the front edge  
of the cabinet (without considering the cabinet  
door).  
Cut as indicated.  
7. Regulate the rear spacer to cover the clearance  
on the rear side once the hood has been  
installed (see also paragraph "Dimensions  
and clearances") and fix it with two screws (one  
per side).  
Spacer  
Spacer  
fixing  
screw  
4. Install the vent system before the range hood. See  
„Venting methods“ and „Dimensions and clear-  
ance“ paragraphs.  
A
Note - for Ductless - recirculating - installations:  
Purchase the Ductless recirculating kit  
Cabinet without ceiling:  
see Dimensions  
and Clearances  
Vent system is not required.  
Cabinet with ceiling:  
A 6" section of duct may be required to connect  
transition to deflector.  
5. Install a conduit long enough to reach the junction  
10  
 
8. Fit the blower unit housing inside the cabinet  
through the bottom opening.  
Check that fixing springs goes over the bottom  
panel..  
Side fixing screws  
Bottom  
opening  
Upper + lower bracket  
definitive fixing screws  
Fixing  
springs  
Bottom  
panel  
.......apply the two bigger brackets (lower brackets)  
under the first two and....  
9. Apply two brackets (one per side) to the blower unit  
housing.........  
Upper bracket  
Lower bracket  
....... lock in place (check that each bracket , once in  
position, is flush to the front side of the blower unit  
housing) tighten the side fixing screws (two per  
brackets) and, from the inside of the hood, fix with  
one screw each then .......  
11  
 
..... tighten securely the two screws on upper  
brackets, check that blower housing is now well  
blocked, then, from the inside of the hood, fix  
definitively the lower brackets with one screw each.  
10. Refinish the installation to cabinet with two fixing  
screws.  
Adjusting  
screws  
Final  
fixing  
screw  
Final  
fixing  
screw  
For Ductless (recirculating) installations  
Cabinet without ceiling ONLY:  
Install the deflector (available as an extra kit) on the  
transition - snap into place.  
Upper + lower bracket  
definitive fixing screws  
11. Connect ducting to transition. Seal with duct tape.  
Do not use duct smaller than the transition.  
For Ductless - recirculating - installations:  
Cabinet with ceiling ONLY:  
provide and install a section of duct long enough to  
connect hood transition to deflector once this has  
been installed onto the cabinet ceiling (the deflec-  
tor is available as an extra kit).  
12  
 
13. For Ductless (recirculating) installations  
12. Electrical connection  
Install one charcoal filter (available as an extra kit).  
WARNING  
Electrical Shock Hazard  
Warning: Turn off power circuit at the service panel  
before wiring this unit.  
120 VAC, 15 or 20 Amp circuit required.  
14. Check all light bulbs to make sure they are secure  
in their sockets.  
Turn power on in service panel.  
Check lights and blower operation.  
15. Install filter.  
ELECTRICAL GROUNDING INSTRUCTIONS  
THIS APPLIANCE IS FITTED WITHAN ELECTRICAL  
JUNCTION BOX WITH 3 WIRES, ONE OF WHICH  
(GREEN/YELLOW) SERVES TO GROUND THE  
APPLIANCE. TO PROTECTYOUAGAINST ELECTRIC  
SHOCK, THE GREEN AND YELLOW WIRE MUST BE  
CONNECTED TO THE GROUNDING WIRE IN YOUR  
HOME ELECTRICALSYSTEM, AND IT MUSTUNDER  
NO CIRCUMSTANCES BE CUT OR REMOVED.  
Failure to do so can result in death or electrical  
shock.  
If range hood does not operate:  
Check that the circuit breaker is not tripped or the  
house fuse blown.  
Disconnect power supply. Check that wiring is  
correct.  
Remove the Junction box cover and knockout and  
install the conduit connector (cULUS listed) in junction  
box cover.  
Run 3 wires; black, white and green ,according to the  
National Electrical Code and local codes and ordi-  
nances, in 1/2" conduit from service panel to junction  
box.  
Connect black wire from service panel to black or red in  
junction box, white to white and green to green-yellow.  
Close junction box cover.  
13  
 
1
2
3
4
5
6
Control panel  
Grease filter  
Grease filter release handle  
Halogen lamp (position and nr. of lamps may vary)  
Sliding Glass  
Hood canopy  
1
5
6
2
3
4
14  
 
Use the high suction speed in cases of concentrated kitchen vapours. It is recommended that the cooker hood suction  
is switched on for 5 minutes prior to cooking and to leave in operation during cooking and for another 15 minutes  
approximately after terminating cooking.  
Description of control panel:  
F
E
D
C
B
A
A
B
C
-
-
-
Lighting: dim lighting / full lighting /off (loop control) - Works even with hood in stand by and/or drawer closed.  
Set Fan in Stand by (LED on the lower side of the display ON).  
ON/OFF Timer for selected speed (visualizes the speed selected and flashing LED on the lower side of the  
display).  
This knob permits the operation of the cooker hood for a established period:  
20 minutes if the speed selected is 1  
15 minutes if the speed selected is 2  
10 minutes if the speed selected is 3  
5 minutes if the boost speed P is selected.  
D
-
Display showing: fan speed (1-2-3-P), filter saturation indicator (F for metal filter, C for charcoal filter)  
Note: if in posses of the Remote Control (see paragraph "List of Part and Accessories") the display shows a  
flashing "b" this to indicate that the remote control battery must be replaced.  
When the led in the lower right side is on, it indicates that the cooker hood is ready for operation (“standby”  
position), the flashing LED indicates that the timer has been activated for selected speed.  
Warning!  
The Charcoal filter saturation function is not activated.  
In order to activate the charcoal filter saturation indicator, press buttons E and F simultaneously for 3 seconds.  
Initially, only letter F will be displayed, then after the 3 seconds have passed, letter C will be displayed as well,  
indicating that the carbon filter saturation control system is active.  
To switch off the system, re-press the same two buttons: letter C appear on display and after 3 seconds it  
disappears and the device will be switched off.  
E
F
-
-
Knob to decrease the speed: from boost speed P to speed level 1.  
Knob to increase (standby) speed to boost speed P.  
Attention! Boost speed P lasts 5 minutes after which the cooker hood automatically sets the speed to level 2  
(suction power).  
Controlling the range hood with sliding glass:  
Closing the glass, all selected speed and lights switched off.  
Hood retains last speed (except P-boost-speed) setting when glass is closed and re-opened.  
If the hood fails to operate correctly, briefly disconnect it from the mains power supply for almost 5 sec. by pulling out the  
plug. Then plug it in again and try once more before contacting the Technical Assistance Service.  
Warning!  
Always press the fan off button A before disconnecting the hood from the mains supply.  
Reset filter saturation signal  
Press knob B for about 3 seconds.  
The letter F and/or C will disappear from the display.  
15  
 
CLEANING  
The cooker hood should be cleaned regularly internally and externally.  
For cleaning use the supplied cloth moistened with a neutral liquid detergents. Avoid abrasive detergents.  
Warning:  
Failure to carry out the basic standards of the cleaning of the cooker hood and replacement of the filters may cause fire  
risks.  
Therefore we recommend observing these instructions.  
GREASE FILTER  
This must be cleaned once a month using non aggressive detergents, either by hand or in the dishwasher, which must  
be set to a low temperature and a short cycle.  
When washed in a dishwasher, the grease filter may discolour slightly, but this does not affect its filtering capacity.  
To remove the grease filter, pull the spring release handle (a-b).  
REPLACING THE LIGHT BULB:  
WARNING  
Disconnect the hood from electricity and be sure the lights are cool.  
If new lights do not operate, make sure the light bulb is inserted correctly before calling service.  
Using a flat head screwdriver or equivalent tool, carefully pry loose the lamp so to unthread from the connector.  
Slide out the lightbulb to be replaced and replace with a new 12V 20W 30° Ø35 GU4 bulb type MR11, “suitable for  
use in open luminarie”.  
16  
 
Issue  
Cause  
What to do  
After installation, the  
unit doesn’t work?  
1. The power source is not turned ON.  
1. Make sure the circuit breaker and the  
unit’s power is ON.  
2. The power line and the cable locking  
connector is not connecting properly.  
2. Check the power connection with the  
unit is connected properly.  
3. The switch board and control board  
wirings are disconnected.  
3. Make sure the wirings between the  
switch board and control board are  
connected properly.  
4. The switch board or control board is  
defective.  
4. Change the switch board or control  
board.  
Light works, but motor is  
not turning.  
1. The motor is defective, possible  
seized.  
1. Change the motor.  
2. The thermally protected system  
detects if the motor is too hot to  
operate and shuts the motor down.  
2. The motor will function properly after the  
thermally protected system cool down.  
3. Damaged condenser.  
3. Change the condenser.  
1. Tighten the motor in place.  
2. Change the blower wheel.  
3. Check the installation of the hood.  
1. Change the halogen bulb.  
2. Tighten the light bulb.  
The unit is vibrating.  
1. The motor is not secure in place.  
2. Damaged blower wheel.  
3. The hood is not secured in place.  
1. Defective halogen bulb.  
2. The light bulb is loose.  
The motor is working,  
but the lights are not.  
The hood is not venting  
out properly.  
1. The hood might be hanging to high  
from the cook top.  
1. Adjust the distance between the cook  
top and the bottom of the hood within  
24” and 32” range.  
2. The wind from the opened windows or  
opened doors in the surrounding area  
are affecting the ventilation of the  
hood.  
2. Close all the windows and doors to  
eliminate the outside wind flow.  
3. Blocking in the duct opening or  
ductwork.  
3. Remove all the blocking from the duct  
work or duct opening.  
4. The direction of duct opening is  
against the wind.  
4. Adjust the duct opening direction.  
5. Using the wrong size of ducting.  
1. Metal filter is loose.  
5. Change the ducting to at least 8” or  
higher.  
Metal filter is vibrating.  
1. Change the metal filter.  
17  
 
TO OBTAIN SERVICE UNDER WARRANTY:  
or any Service Related Questions, please call:  
1-888-880-8368  
Staple your receipt here.  
Proof of the original purchase  
date is needed to obtain service  
under the warranty.  
TO OBTAIN SERVICE UNDER WARRANTY: You must present proof of original purchase date.  
Please keep a copy of your dated proof of purchase (sales slip) in order to obtain service under warranty.  
One Year Service Repair Warranty:  
For one year from date of original purchase, we will provide free of charge, service labor to repair any failed  
parts or components due to manufacturing defects.  
One Year Parts Warranty:  
For one year from date of original purchase, we will provide free of charge, nonconsumable replacement  
parts or components that failed due to manufacturing defects. Consumable parts not covered by this warranty  
include: Light Bulbs, Metal and Carbon Filters.  
Who is Covered:  
This warranty is extended to the original purchaser for products purchased for ordinary home use in the 48  
mainland states, Hawaii and Washington D.C. In Canada and Alaska, this warranty is Limited. There might  
be costs associated with shipping the products to our designated service locations or you might need to pay  
service technician’s travel costs, to have the appliance repaired in-home.  
This Warranty will be Voided when:  
Product damaged through negligence, misuse, abuse, accident. Improper installation and failure to follow  
installation instructions.  
When product is used commercially or other than its intended purpose. Damaged because of improper  
connection with equipment of other manufacturers. Repaired or modified by anyone other than Zephyr’s  
Authorized Agents.  
What is Not Covered:  
Consumable parts such as light bulbs, filters, and fuses. Services outside of service area and the labor cost  
incurred in connection with the removal, shipping and reinstallation cost, nor does it cover any other  
contingent expenses. The natural wear of finish, and wear due to improper maintenance, use of corrosive  
and abrasive cleaning products, pads, and oven cleaner products. Chips, dents or cracks due to abuse,  
misuse, freight damage, or improper installation. Service trips to your home to teach you how to use the  
product. Damage of product caused by accident, fire, floods or act of God.  
This warranty is valid in the United States and Canada. It is non-transferable and applies only to the original  
purchaser and does not extend to subsequent owners of this product. Any applicable implied warranties,  
including the warranty of merchantantability, are limited in duration to a period of express warranty as  
provided herein beginning with the date of original purchase at retail and, no warranties, whether express or  
implied, shall apply to this product thereafter.  
Have your product proof of purchase with date ready for warranty issues.  
Or write to:  
Zephyr Corporation  
Service and Warranty Department  
395 Mendell Street  
San Francisco, CA 94124  
 
Part Description  
Part#  
halogen bulb, 12V 20 W  
Z0B-0013  
metal filter  
GF02ZA  
Part Description  
Part#  
Ductless Recirculating Kit  
charcoal replacement filter  
ZRC-00GL  
Z0F-C063  
remote control  
19  
 
20  
 

Weslo Treadmill WLTL29013 User Manual
Westinghouse Landscape Lighting W 019 User Manual
Whirlpool Microwave Oven GMH5205XVB User Manual
Williams Furnace 07435 User Manual
Wolf Griddle IRG 36 User Manual
Woods Equipment Compact Loader 2104045 User Manual
Xilinx Life Jacket 82i User Manual
Yamaha CD Player CDC 95 User Manual
Zanussi Fryer 178059 User Manual
Zanussi Washer FX 1165 W User Manual